Inspection
Inspection Details
Equipment ID
8785
8785
Inspection Date
4/28/2025
4/28/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Daniel Schook
Daniel Schook
Relief Valve Pressure
310
310
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14
14
External ID
b7d09eef-43e9-421f-84a8-cbd9e9ba1d63
b7d09eef-43e9-421f-84a8-cbd9e9ba1d63
Location
Corporate Plaza Bldg
14528 S Outer 40 Rd, Chesterfield, MO
Phone: (314) 336-2362
14528 S Outer 40 Rd, Chesterfield, MO
Phone: (314) 336-2362
Owner
Attn: C/O NEWMARK
GAHC3 Chesterfield Corporate Plaza, LLC
14528 S. Outer 40 Rd., Suite 10, Chesterfield, MO 63017
Phone: (636) 293-9114
Email: Chelsey.lamoreaux@nmrk.com
GAHC3 Chesterfield Corporate Plaza, LLC
14528 S. Outer 40 Rd., Suite 10, Chesterfield, MO 63017
Phone: (636) 293-9114
Email: Chelsey.lamoreaux@nmrk.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Remove oil from pit floor | 12/2/2019 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Repair Car door restrictors | 9/10/2019 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Post current State certificate in machine room | 12/2/2019 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Repair/replace control valve | 12/2/2019 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current operating certificate in machine room. | 11/1/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Maintenance control program shall include written procedures for inspections and test on site. | 11/1/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Current means to collect oil has no lid. | 8/16/2024 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Observed oil in sump hole, remove. Determine if sump still works, replace if needed. | 8/16/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | None | 8/16/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Current means to collect oil has no lid, provide. | 8/16/2024 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Observed oil in the sump hole, remove. | 8/16/2024 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Determine if the sump pump still works, if not replace. | 8/16/2024 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 8/16/2024 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current State operating permit shall be obtained and displayed in the equipment room. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Adjust upthrust roller bearings for proper clearance to door hanger track (all floors). | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Compliant/required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures. No documentation found for 2022 through 2025. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Fire service operation shall be tested monthly and documented on fire service testing log. No log present. | |||
MO Minimum : Elevators | (I) - Pits | (I)8 | Determine if the sump pump still works. If not, replace. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Pump motor and/or pump making extremely loud noise while running. Investigate and repair/replace as needed. |