Inspection
Inspection Details
Equipment ID
8786
8786
Inspection Date
4/29/2025
4/29/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Daniel Schook
Daniel Schook
Relief Valve Pressure
400
400
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
1750085b-f556-49c4-9eef-a65fc6eeb1b9
1750085b-f556-49c4-9eef-a65fc6eeb1b9
Location
Corporate Plaza Bldg
14528 S Outer 40 Rd, Chesterfield, MO
Phone: (314) 336-2362
14528 S Outer 40 Rd, Chesterfield, MO
Phone: (314) 336-2362
Owner
Attn: C/O NEWMARK
GAHC3 Chesterfield Corporate Plaza, LLC
14528 S. Outer 40 Rd., Suite 10, Chesterfield, MO 63017
Phone: (636) 293-9114
Email: Chelsey.lamoreaux@nmrk.com
GAHC3 Chesterfield Corporate Plaza, LLC
14528 S. Outer 40 Rd., Suite 10, Chesterfield, MO 63017
Phone: (636) 293-9114
Email: Chelsey.lamoreaux@nmrk.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Remove Oil from pit floor | 12/2/2019 |
| conversion | conversion | n/a | No | No | Repair Fire Service--Car does not come off fire service when Phase I switch is placed in bypass | 12/2/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Make car door restrictors operational | 9/10/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace sections of missing duct covers in hoistway between L & 1st floor | 12/2/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Post current State certificate in machine room | 12/2/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance control program shall include written procedures for inspections and test on site. | 11/1/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 11/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | None | 6/14/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/14/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | OSV in the pit is due for testing, provide. | 4/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car door restrictor shall work at all floors. | 5/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State operating permit shall be obtained and displayed in the equipment room. | 5/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures. No documentation found for 2022 through 2025. | 5/16/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service operation shall be tested monthly and documented on fire service testing log. No log present. | 5/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (all floors). | 5/16/2025 |