|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
No
|
No
|
Replace missing bottom restrictor angles on levels 2 and 4
|
9/10/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
8.11.2.1.3(m)
|
No
|
Yes
|
Replace missing cutter pins on counterweights. Ropes jumped out of grooves on counterweight sheave.
|
6/4/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Alarm bell does not work.
|
6/4/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency light and alarm bell do not work.
|
10/28/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
Yes
|
No
|
The car door restrictor bracket is missing on the 4th floor hoistway door and will not properly catch/restrict the opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection and repair is required.
|
8/21/2024
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
No
|
No
|
Pit ladder is covered by screening making the ladder unusable.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required.
|
8/21/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Audible alarm in car is inoperable and shall be repaired for reinspection.
|
5/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection)
|
Yes
|
No
|
Audible signal during initial recall is inoperable and shall be repaired for reinspection.
|
5/22/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
Door open button inoperable and shall be repaired for reinspection.
|
|