Inspection
Inspection Details
Equipment ID
6925
6925
Inspection Date
5/19/2025
5/19/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
NA
NA
Slide
Instantaneous
Instantaneous
Governor Rope Pull
150/600
150/600
Door Closing Force
25
25
External ID
8fcdd72c-ea19-4b4a-b847-d87b9e463c4d
8fcdd72c-ea19-4b4a-b847-d87b9e463c4d
Location
Normandy Nursing Home
7301 Saint Charles Rock Rd, St. Louis, MO
Phone: (314) 862-0555
7301 Saint Charles Rock Rd, St. Louis, MO
Phone: (314) 862-0555
Owner
Attn: Normandy Nursing Home
Normandy Nursing Home
7301 Saint Charles Rock Rd, St. Louis, MO 63133
Phone: (000) 000-0000
Email: alyhardin@mgmhealthcare.com
Normandy Nursing Home
7301 Saint Charles Rock Rd, St. Louis, MO 63133
Phone: (000) 000-0000
Email: alyhardin@mgmhealthcare.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The lobby door gibs need replacing. | 4/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 6/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 4/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/15/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 12/15/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 12/15/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The lighting in the machine room shall be not less than 10 foot-candles at the floor level. | 12/15/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 12/15/2023 |
| A17.1-2016 : Elevators | 2.19 Gears, Bearings, and Flexible Couplings | 8.11.2.1.2(v) | No | No | Correct the oil leaks on the hoist machine. | 12/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be kept clean. | 12/15/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Stairwell leading to machine room has insufficient lighting. It must be at least 19 foot-candles. | 12/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. They could hear the inspector, but could not establish communication. | 6/30/2025 |