Inspection
Inspection Details
Equipment ID
4219
4219
Inspection Date
12/11/2018
12/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Donald Brown
Donald Brown
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
10
10
External ID
2948e445-5a7d-4c79-be9a-6b10fbf16402
2948e445-5a7d-4c79-be9a-6b10fbf16402
Location
Truman Farm Villa Apt
5302 HARRY S TRUMAN DR, GRANDVIEW, MO
5302 HARRY S TRUMAN DR, GRANDVIEW, MO
Owner
Steadfast Companies
5300 HARRY S TRUMAN DR, GRANDVIEW, MO 64030-1783
5300 HARRY S TRUMAN DR, GRANDVIEW, MO 64030-1783
Billing
Attn: Truman Farm Villas
5300 HARRY S TRUMAN DR, GRANDVIEW, MO 64030-1783
5300 HARRY S TRUMAN DR, GRANDVIEW, MO 64030-1783
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | replace hoistway door pickup rollers that are missing on the top and bottom floors | 2/4/2019 | |
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service test and post the log in the machine room | 1/23/2020 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post a new copy of the state operating certificate in the elevator machine room every year | 2/11/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | fire caulk all penetrations in the machine room walls to maintain the fire rating of the room, new holes have been made that were not fire caulked | 2/11/2021 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | monthly fire service test log is not posted in the machine room, perform fire service test monthly and keep a test log in the machine room | 1/27/2022 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | water and oil mixture in the pit, maintain a dry pit, clean up the pit | 12/27/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | emergency phone had a dial tone and dialed a number then it went to a busy signal and hangs up without connecting to answering service | 12/19/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | In case of fire don't use elevator signage needed | 3/7/2024 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting below 10 foot candles | 3/7/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher out of date | 3/7/2024 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs cleaning | 3/7/2024 | ||
MO Minimum : Elevators | (I) - Pits | (I)8 | Sump hole needs cover | 3/7/2024 |