Inspection
Inspection Details
Equipment ID
4220
4220
Inspection Date
12/11/2018
12/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Donald Brown
Donald Brown
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
b0d5090f-6662-4650-8ce5-65f337390db8
b0d5090f-6662-4650-8ce5-65f337390db8
Location
Truman Farm Villas
5304 HARRY S TRUMAN DR, GRANDVIEW, MO
5304 HARRY S TRUMAN DR, GRANDVIEW, MO
Owner
Steadfast Companies
5300 HARRY S TRUMAN DR, GRANDVIEW, MO 64030-1783
5300 HARRY S TRUMAN DR, GRANDVIEW, MO 64030-1783
Billing
Attn: Truman Farm Villas
5300 HARRY S TRUMAN DR, GRANDVIEW, MO 64030-1783
5300 HARRY S TRUMAN DR, GRANDVIEW, MO 64030-1783
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | replace missing hoistway door pick up rollers on the top and bottom landings | 2/4/2019 | |
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service test and post the log in the machine room | 1/23/2020 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | repair machine room door lock and door jamb, door jamb broke because the door lock would not open all the way | 1/23/2020 | ||
A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post a new copy of the state operating certificate in the elevator machine room every year | 2/11/2021 | ||
A17.1-2016 : Elevators | 2.4 - Machine space | 8.11.3.1.2(g) | Fire caulk all penetrations in the machine room walls to maintain the fire rating of the room, new holes have been made that were not fire caulked | 2/11/2021 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | monthly fire service test log is not posted in the machine room, perform fire service test monthly and keep a test log in the machine room | 1/27/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | phone line is dead, cable modem is not working, provide working phone line | 12/19/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | In case of fire don't use elevator signage needed | 5/14/2024 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting below 10 foot candles | 5/14/2024 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Non elevator equipment stored in machine room | 5/14/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher out of date | 5/14/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Plunger has very noticeable knock around 2nd floor. | 5/14/2024 |