Inspection
Inspection Details
Equipment ID
8784
8784
Inspection Date
5/21/2025
5/21/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Daniel Schook
Daniel Schook
Relief Valve Pressure
400
400
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14
14
External ID
ffcdd924-dca6-4005-be41-26f1caf087fd
ffcdd924-dca6-4005-be41-26f1caf087fd
Location
Corporate Plaza Bldg
14528 S Outer 40 Rd, Chesterfield, MO
Phone: (314) 336-2362
14528 S Outer 40 Rd, Chesterfield, MO
Phone: (314) 336-2362
Owner
Attn: Sansone Group/Nova 40
Chesterfield Corporate Plaza, LLC
120 S. Central Ave., Ste. 500, Clayton, MO 63105
Phone: (000) 000-0000
Email: sansonehelpdesk@sansonegroup.com
Chesterfield Corporate Plaza, LLC
120 S. Central Ave., Ste. 500, Clayton, MO 63105
Phone: (000) 000-0000
Email: sansonehelpdesk@sansonegroup.com
Billing
Attn: Novus Companies/Nova 40
Chesterfield Corporate Plaza, LLC
20 Allen Ave., Ste. 400, Webster Groves, MO 63119
Phone: (000) 000-0000
Email: nhoeing@novusdev.com
Chesterfield Corporate Plaza, LLC
20 Allen Ave., Ste. 400, Webster Groves, MO 63119
Phone: (000) 000-0000
Email: nhoeing@novusdev.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Replace missing gib on 1st & 3rd floor hoistway door | 12/2/2019 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Post current state certificate in machine room | 12/2/2019 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Car door restrictor does not work. | 2/2/2021 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Maintenance control program shall include written procedures for inspections and tests on site. | 11/1/2020 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No current state operating certificate on display in machine room. | 11/1/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | None | 6/14/2024 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 6/14/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Victraulic fitting below valve assembly is bad, repair as needed. | 6/14/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Selector rope tail sheave in the pit excessively noisy. | 6/14/2024 | ||
A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | x | OSV in the pit is due for testing, provide. | 4/28/2025 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | x | Victaulic fitting below valve assembly is bad, repair as need. This violation was previously marked as "fixed" in the database but was not. As of 4/28/25, fitting is severely spraying high pressure hydraulic fluid. Red Tag Issued. | 5/21/2025 |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | 2-way communication device shall work. No dial tone. | 5/21/2025 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current State operating permit shall be obtained and displayed in the equipment room. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Adjust upthrust roller bearings for proper clearance to door hanger track (all floors). | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Compliant/required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures. No documentation found for 2022 through 2025. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Fire service operation shall be tested monthly and documented on fire service testing log. No log present. |