Inspection
Inspection Details
Equipment ID
7662
7662
Inspection Date
5/2/2025
5/2/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Christian Schickedanz
Christian Schickedanz
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
e6156711-937a-4cb0-af26-c909cd04ce71
e6156711-937a-4cb0-af26-c909cd04ce71
Location
Fox Theater
527 N Grand Blvd, St. Louis, MO
Phone: (314) 534-1678
527 N Grand Blvd, St. Louis, MO
Phone: (314) 534-1678
Owner
Attn: John Wolf
Fox Associates, LLC
539 N Grand Blvd, St. Louis, MO 63103
Phone: (314) 657-5060
Alt Phone: (314) 308-3972
Email: john@foxstl.com
Fox Associates, LLC
539 N Grand Blvd, St. Louis, MO 63103
Phone: (314) 657-5060
Alt Phone: (314) 308-3972
Email: john@foxstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | Yes | No | Walk in pit door shall have safety switch installed. | 2/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall work. | 2/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log, and fire service log recorded monthly. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Reinstall covers on rope gripper. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 1/14/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | UNIT IS RED-TAGGED BECAUSE THE ROPE GRIPPER DID NOT WORK WHEN TESTING THE UNINTENDED MOVEMENT UP. | 5/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Reinstall covers on rope gripper. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self locking. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | No | No | Walk in pit door shall have safety switch. | 1/14/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel | Yes | No | FEO Phase II, hold does not work. Shall not accept car calls while in HOLD. |