Inspection
Inspection Details
Equipment ID
19439
19439
Inspection Date
5/27/2025
5/27/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
aeace5d2-620a-4ed5-b925-5d848c6e43ba
aeace5d2-620a-4ed5-b925-5d848c6e43ba
Location
The Crescent
153 Carondelet Plz, Clayton, MO
Phone: (314) 727-3900
Email: Jvanmier@thecrescentcondo.com
153 Carondelet Plz, Clayton, MO
Phone: (314) 727-3900
Email: Jvanmier@thecrescentcondo.com
Owner
Attn: The Crescent Condominium
The Crescent Condominium
155 Carondelet Plz, Ste 100, Clayton, MO 63105
Phone: (000) 000-0000
Email: jblair@thecrescentcondo.com
The Crescent Condominium
155 Carondelet Plz, Ste 100, Clayton, MO 63105
Phone: (000) 000-0000
Email: jblair@thecrescentcondo.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. | 8/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Clean pit. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | No | No | Car top outlet has open neutral, repair as needed. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Light at top of hoistway does not work. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Car does not have emergency brake cable system. Provide and retest. | 7/5/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing needs to be completed, was only able to conduct the annual portion of test. | 7/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | Yes | No | Hoistway access switch is not operating correctly at the 2nd floor. Re-inspection required | 9/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device has failed, needs repaired. Re-inspection required | 9/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 6/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Provide for counterweight derailment device to work | 6/2/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | 8/18/2026 |
| A17.1-2016 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | No | No | The drop ceiling shall have a way for emergency evacuation | 8/18/2026 |