Inspection
Inspection Details
Equipment ID
8164
8164
Inspection Date
5/15/2025
5/15/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
46b17d59-b1cd-4c54-b6ee-a3bd117f6f23
46b17d59-b1cd-4c54-b6ee-a3bd117f6f23
Location
School of Medicine
1402 S Grand Blvd, St. Louis, MO
Phone: (314) 977-2954
1402 S Grand Blvd, St. Louis, MO
Phone: (314) 977-2954
Owner
Attn: Alex Del Vecchio
St. Louis University
3545 Lindell Blvd, 2nd Fl, St. Louis, MO 63103
Phone: (314) 977-2966
Email: alexander.delvecchio@slu.edu
St. Louis University
3545 Lindell Blvd, 2nd Fl, St. Louis, MO 63103
Phone: (314) 977-2966
Email: alexander.delvecchio@slu.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist cables due to diameter reduction and breakage. 30-day compliance or red tagged. | 6/18/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Car door shall not open automatically, only with constant pressure on Phase II | 6/15/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Repair fire recall Phase I. Door automatically opens at floor and call cancel doesn't cancel call. | 8/31/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace the governor cable that is about to break in two places. | 8/31/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Repair fire recall phase 2. Door auto opens at floor and call cancel does not work | 11/2/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace governor cable. Cable about to break in two | 11/2/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide existing pit light to work. | 9/4/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide proper working Phase I operations, door failed to open upon recall.(‘96. 211.3) | 6/6/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide existing Phase II operations to work properly. Went to lowest floor, doors opened automatically.(‘96. 211.3) | 6/6/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Machine room disconnects shall have feed location labels. | 5/15/2025 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | Suspension ropes to be shortened to allow for proper "runby". Currently only 4.5" of runby and shall be between 6" - 12". | 5/15/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | FAID shall be tested. | 5/15/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | This elevator is connected to an emergency generator and shall be tested while operating on the generator. Generator is currently out of service and parts are on order. | 5/15/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | This elevator is connected to an emergency generator and shall be tested while operating on the generator. Generator is currently out of service and parts are on order. All other acceptance testing has passed. | 8/5/2025 |