Inspection
Inspection Details
Equipment ID
953
953
Inspection Date
5/30/2025
5/30/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Stephen Long
Stephen Long
Relief Valve Pressure
na
na
Slide
16"
16"
Governor Rope Pull
710/ 1300
710/ 1300
Door Closing Force
26
26
External ID
93141837-73e8-4764-8a42-02ac9beb63c8
93141837-73e8-4764-8a42-02ac9beb63c8
Location
Southwest Power Station
FARM ROAD 115 & 164, SPRINGFIELD, MO
Phone: (417) 761-4932
FARM ROAD 115 & 164, SPRINGFIELD, MO
Phone: (417) 761-4932
Owner
Attn: Tyler Peck
City Utilities of Springfield
301 E Central St, Springfield, MO 65802
Phone: (417) 831-8492
Email: Tyler.Peck@cityutilities.net
City Utilities of Springfield
301 E Central St, Springfield, MO 65802
Phone: (417) 831-8492
Email: Tyler.Peck@cityutilities.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Car door exceeds 30 pounds of torque- Reduce to under 30 pounds | 6/4/2019 |
| conversion | conversion | n/a | No | No | Replace pit light | 6/4/2019 |
| conversion | conversion | n/a | No | No | Emergency light and bell doesn't work . | 6/4/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as there is no dial tone. | 8/6/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace the light tubes in the car ceiling. | 8/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace the missing braile plates floor 1 and 2 | 8/6/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace the burnt out light tubes in the machine room. | 8/6/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 8/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Replace the worn door gibbs the door is draging | 10/27/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace the missing light tubes in the car ceiling. | 2/3/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 8.11.2.1.3(z) | No | No | Replace the badly roughed govenor rope | 7/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 8.11.2.1.3(z) | No | No | Replace the very badly rouged governor rope due to excessive rouging. | 7/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace the compensation rope due to excessive damage to the covering in many places. | 2/3/2026 |
| MO Minimum : Elevators | (N) - Guide Rails | (N)2 | No | No | Repair or replace the lower sections of both guide rails due to excessive rusting from standing water in the pit. | 2/3/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Repair or replace both of the buffers due to excessive rust damage due to standing water in the pit. | 2/3/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace the govoner rope due to excessive rouging and broken wire lays near the bottom . | 5/31/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | Repair the damaged comp chain jacket, as it has been snagged and damaged. | 2/3/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Replace the burnt out pit light. | 2/3/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | replace the burnt out light tubes in the machine room ceiling , you are to provide a minimum of 20 ftc at the machine room floor. | 2/3/2026 |