Inspection
Inspection Details
Equipment ID
638
638
Inspection Date
5/28/2025
5/28/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Leonard Morris
Leonard Morris
Relief Valve Pressure
450
450
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
8cad9f6d-9eaa-4be7-a067-e111789890d2
8cad9f6d-9eaa-4be7-a067-e111789890d2
Location
John Knox Village- East
1201 W 19th St, Higginsville, MO
Phone: (660) 584-7111
1201 W 19th St, Higginsville, MO
Phone: (660) 584-7111
Owner
Attn: Scott Baer
John Knox Village-East-Meyer Foundation
1201 W 19th St, Higginsville, MO 64037
Phone: (000) 000-0000
Email: scottbaer@johnknoxvillageeast.com
John Knox Village-East-Meyer Foundation
1201 W 19th St, Higginsville, MO 64037
Phone: (000) 000-0000
Email: scottbaer@johnknoxvillageeast.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-closing and self-locking | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | The Hydraulic pump unit seals appears to be leaking as well as the unit muffler bolts. This is creating an overflow of the pump oil containment pan. | 3/25/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Oil overflowed pan. Clean pan and floor | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher out of date | 3/25/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting below standard | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The hydraulic pump, valve and/muffler leaking. Repair with seals and/or tighten all fittings and bolts | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Excessive packing leakage. Replace | 3/25/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs cleaning from oil bucket overflowed because of excessive packing leakage | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not dialing out | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room has inadequate lighting | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Machine room oil pan full. Clean and repair leaks on pump ,valve or muffler. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room needs fire extinguisher |