Inspection
Inspection Details
Equipment ID
18764
18764
Inspection Date
6/5/2025
6/5/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
N/A
N/A
Slide
16.5
16.5
Governor Rope Pull
100/290
100/290
Door Closing Force
24
24
External ID
d9fd0403-4d30-4026-87b7-aacd97638b3a
d9fd0403-4d30-4026-87b7-aacd97638b3a
Location
Horseshoe Casino
999 N 2nd St, St. Louis, MO
Phone: (314) 881-7782
999 N 2nd St, St. Louis, MO
Phone: (314) 881-7782
Owner
Attn: Andy Nowell
Horseshoe Casino
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-7782
Email: anowell@caesars.com
Horseshoe Casino
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-7782
Email: anowell@caesars.com
Billing
Attn: Andy Nowell
Horseshoe Casino
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-7782
Email: anowell@caesars.com
Horseshoe Casino
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-7782
Email: anowell@caesars.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Repair bent safety actuating link rod on car crosshead. (Governor sheave gauge bottoms on "C" measurement). | 1/15/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm button on Main COP not working. | 11/18/2019 |
| A17.1-1996 : Elevators | 2.29 - Car and counterweight safeties | 1002.2b | Yes | Yes | Safety rod bent on top of the elevator. Did NOT red tag. Reinspect only. | 11/18/2019 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1200.4d | Yes | No | Suspension belts showing rouge. Monitor shows replacement. Replace belts in 60 days. | 11/18/2019 |
| A17.1-1996 : Elevators | 2.29 - Car and counterweight safeties | 1002.2b | Yes | Yes | Repair bent safety actuating link rod on car crosshead. | 1/22/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Coated steel belt monitor communication disabled. Communication re-established but no maintenance records found of this, or any other event, in elevator equipment room. Provide unit maintenance records. | 12/8/2025 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | Yes | No | Belt monitor showing bad belts, Unit turned off. Re-inspection required | 5/31/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire Service Phase 1 & 2 must be tested, Re-inspection required | 5/31/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | No | No | door to access pit equipment shall be lockable to prevent access by non elevator personnel | 12/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm shall work | 7/22/2024 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.18.1 | Yes | Yes | Overspeed governor exceeded maximum allowable pull through measurement. Red tagged. Replace governor and governor rope and retest | 7/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Coated steel belt monitor communication was disabled. Communication was re-established, but no maintenance records found of this or any other event in elevator machine room. provide unit maintenance records | 12/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement | 7/22/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | Yes | Yes | The hoist belt monitoring system is disabled with visible rouge present on the hoist belts. The hoist belts shall be replaced with the hoist belt monitoring being re-enabled with an alteration permit being issued and a reinspection performed before the elevator shall be returned to service. | 6/5/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm shall work. | 6/5/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | No | No | door to access pit equipment shall be lockable to prevent access by non elevator personnel | 12/8/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two-way communication are inoperable and shall be repaired, or replaced. | 12/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Fire service Phase I operation instructions in main lobby are rubbed off, need to replace signage. | 12/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | T Cable showing signs of wear. Repair or replace. | 12/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Pit light not working | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working |