Inspection
Inspection Details
Equipment ID
23675
23675
Inspection Date
6/6/2025
6/6/2025
Inspection Type
Alteration
Alteration
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
0dc5c05d-1a1f-4f19-b3b8-369e9b54b3e2
0dc5c05d-1a1f-4f19-b3b8-369e9b54b3e2
Location
Vanguard Clayton
8500 Maryland Ave, Clayton, MO
Phone: (314) 410-5213
8500 Maryland Ave, Clayton, MO
Phone: (314) 410-5213
Owner
Attn: Glenn Barnd
Barton Apartments SPE,LLC
8500 Maryland Avenue, St. Louis, MO 63124
Phone: (314) 410-5213
Email: bslmanager@carterhaston.com
Barton Apartments SPE,LLC
8500 Maryland Avenue, St. Louis, MO 63124
Phone: (314) 410-5213
Email: bslmanager@carterhaston.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 8/28/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Call cancel push button shall work. Did NOT red tag. Reinspect only. | 8/28/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Incomplete annual inspection. Perform fire service testing. | 3/31/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10 Emegency Operation and Signaling Devices | Yes | No | Perform uncontrolled motion test. | 3/31/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work on emergency power or normal power. Repair or replace | 10/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | Governor remote trip / reset inoperable, needs repaired. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Check governor rope pull out and pull through force. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Check governor switch and jaws tripping speed. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test drive machine with 125% of rated load. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car safeties at rated speed with rated load. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test unintended car movement with 125% of rated load. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test elevator on emergency power. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean debris form elevator pit | 10/19/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean dirt from elevator car top | 10/19/2023 |