Inspection
Inspection Details
Equipment ID
1541
1541
Inspection Date
6/3/2025
6/3/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
7e15e96c-1e92-4fd3-8008-283c3ae5d827
7e15e96c-1e92-4fd3-8008-283c3ae5d827
Location
Whitehall Club
710 S Hanley Rd, Clayton, MO
Phone: (314) 863-7555
710 S Hanley Rd, Clayton, MO
Phone: (314) 863-7555
Owner
Attn: Whitehall Club (Bob Swehla)
Whitehall Club
710 S Hanley Rd, Clayton, MO 63105
Phone: (314) 863-7555
Email: bob.swehla2@gmail.com
Whitehall Club
710 S Hanley Rd, Clayton, MO 63105
Phone: (314) 863-7555
Email: bob.swehla2@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 9/24/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Elevator pit is full of water. Repair sump pump. | 5/26/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the state operating certificate shall be displayed in the machine room | 2/23/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work | 2/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired. Replace or have serviced | 2/23/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to machine room shall not be blocked | 2/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light shall work. Re-inspection required | 5/30/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Re-install cover on fan electrical box on cartop | 2/23/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 2/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light does not work. Re-inspection required | 7/2/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency standby power needs to be tested on the elevator. Re-inspection required | 6/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is inoperable. Re-inspection required | 7/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm shall be made to operate without 110 vac. Re-inspection required | 7/24/2026 |