Inspection
Inspection Details
Equipment ID
26922
26922
Inspection Date
6/3/2025
6/3/2025
Inspection Type
New Installation
New Installation
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Dustin Black
Dustin Black
Relief Valve Pressure
600
600
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
9749db32-7013-47e9-af42-e3bd55313cd3
9749db32-7013-47e9-af42-e3bd55313cd3
Location
DEVON STORAGE ST LOUIS
4222 UNION BLVD, St. Louis, MO
Phone: (888) 553-3866
Email: terry@ramgcd.com
4222 UNION BLVD, St. Louis, MO
Phone: (888) 553-3866
Email: terry@ramgcd.com
Owner
Attn: DEVON SELF STORAGE
DEVON SELF STORAGE
2000 POWELL ST STE 1240, EMERYVILLE, CA 94608
Phone: (888) 553-3866
Email: terry@ramgcd.com
DEVON SELF STORAGE
2000 POWELL ST STE 1240, EMERYVILLE, CA 94608
Phone: (888) 553-3866
Email: terry@ramgcd.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Install emergency two-way communications device in car. | 6/18/2025 | |
| A17.1-2016 : Elevators | 3.3 - Top-of-car operating device | 2.14.1.7 | x | Install railing on cartop. | 6/18/2025 | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | x | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 6/18/2025 | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/18/2025 | |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Conduit carrying incoming power to pump unit must be raised to allow for future pump/motor replacement. Components cannot be replaced where the pipe is currently located. | 6/18/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | x | Heat detector in machine room is more than 24" from sprinkler head and needs to be moved. | 6/18/2025 | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | x | Patch holes in machine room. | 6/18/2025 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Fire caulk and fill voids on hoistway side of entrance frames. | 6/18/2025 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Fire caulk and seal around room side of entrance frames. | 6/18/2025 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Fire caulk around sprinkler pipe where it passes into front of hoistway above first floor entrance. | 6/18/2025 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Seal around ductwork where it passes between hoistway wall above first floor entrance. | 6/18/2025 | |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | x | Patch holes around hydraulic supply line and sump pump discharge line at pit floor level. | 6/18/2025 | |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Remove old unused sprinkler piping from overhead. | 6/18/2025 | |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | x | Top of common wall between hoistways shall be beveled no less than 75 degrees. | 6/18/2025 |