Inspection
Inspection Details
Equipment ID
19774
19774
Inspection Date
6/4/2025
6/4/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Donald Miles
Donald Miles
Relief Valve Pressure
490
490
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
5c242ac3-ecaf-4e54-8f2c-cc7f87729bf2
5c242ac3-ecaf-4e54-8f2c-cc7f87729bf2
Location
West Hills Community Church
13250 S Outer 40 Rd, Town & Country, MO
Phone: (314) 434-5963
Alt Phone: (314) 504-7827
13250 S Outer 40 Rd, Town & Country, MO
Phone: (314) 434-5963
Alt Phone: (314) 504-7827
Owner
Attn: West Hills Community Church
West Hills Community Church
13250 S Outer 40 Rd, Town and County, MO 63017
Phone: (314) 434-5963
Email: mail@westhillsstl.org
West Hills Community Church
13250 S Outer 40 Rd, Town and County, MO 63017
Phone: (314) 434-5963
Email: mail@westhillsstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate shall be displayed in machine room. | 9/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be provided on-site. | 9/27/2022 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV sealed, no tag. Due for testing. | 11/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | Provide means to collect oil in the pit from each piston. Remove lines going back to tank. | 11/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | The elevator is equipped with an overspeed valve. Category 5 testing was due in 2022. A category 5 test of the overspeed valve shall be completed within 90 days. | 11/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current test & tagged ABC type fire extinguisher shall be provided in the machine room. | 11/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 11/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation and the date shall be available on site. Note: No entries have been made since 2023. | 7/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. Note: Per the state of Missouri: The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals, and "machine rooms cannot be used as containment areas". A gravity feed system is being used and is not allowed. | 7/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | No | No | Jack head drain tube shall be routed to measurable containers in pit. Currently tubes are routed into buckets located in the machine room. These buckets shall be relocated to the pit. | 6/1/2026 |