Inspection
Inspection Details
Equipment ID
7156
7156
Inspection Date
6/11/2025
6/11/2025
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Vincent Langendoerfer
Vincent Langendoerfer
Relief Valve Pressure
NA
NA
Slide
20
20
Governor Rope Pull
100/590
100/590
Door Closing Force
15
15
External ID
1bb1924f-0121-4c00-8cbf-456de08dee5b
1bb1924f-0121-4c00-8cbf-456de08dee5b
Location
HoteLumiere
901 N 1st St, St. Louis, MO
Phone: (314) 881-7777
901 N 1st St, St. Louis, MO
Phone: (314) 881-7777
Owner
Attn: Pinnacle Entertainment
Pinnacle Entertainment
3800 Howard Hughes Pkwy, Las Vegas, NV 89169
Phone: (000) 000-0000
Pinnacle Entertainment
3800 Howard Hughes Pkwy, Las Vegas, NV 89169
Phone: (000) 000-0000
Billing
Attn: Andy Nowell
HoteLumiere
901 N 1st St, St. Louis, MO 63102
Phone: (314) 881-7870
Email: anowell@caesars.com
HoteLumiere
901 N 1st St, St. Louis, MO 63102
Phone: (314) 881-7870
Email: anowell@caesars.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need repair. Need lighting in front of #4 controller where there is none. 10 ft candle minimum. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door needs to be self closing and locking. | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working on battery power. | 12/12/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean oil off of floor. | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated cert in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Suspension means, diameter loss due to wear exceeds retirement criteria. | 5/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light, phone and alarm bell shall work. | 5/1/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need repair. 10 ft candle minimum | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door needs to be self closing and locking | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display state operating certificate in the machine room | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. REINSPECT REQUIRED | 4/19/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Door closing force is to high | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work with power off. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self locking / self closing | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting inadequate | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, needs serviced or replaced | 1/23/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 6/11/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Fire extinguisher is out of date. | 11/26/2025 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.18.3 | Yes | No | Governor shall be sealed | 11/26/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Vent shaft at top of HW has a ledge greater than 4". Shall be beveled or screened to remove ledge. 2.1.6.2 | 11/26/2025 |