Inspection
Inspection Details
Equipment ID
15441
15441
Inspection Date
6/13/2025
6/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Zachary Thieme
Zachary Thieme
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
c9530061-af4b-473f-bb3a-bc53ff02bf6e
c9530061-af4b-473f-bb3a-bc53ff02bf6e
Location
Park Lane Apartments
4907 W Pine Blvd, St. Louis, MO
Phone: (314) 304-3747
4907 W Pine Blvd, St. Louis, MO
Phone: (314) 304-3747
Owner
Attn: Revival STL Construction, LLC
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | Test the car safeties and provide means (tool) to wind up safeties for testing. | 5/5/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)4 | x | Provide bottom door guides on "B" floor hoistway door. | 9/15/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Replace or repair all hoistway door glass vision panels as needed. | 9/15/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Remove fluids from the pit. Provide means of waterproofing to prevent further entry of fluids. | 9/15/2021 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)10 | Provide code compliant hoistway access. | 9/15/2021 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | Provide means to substantially level floor. Pull out hole creates a tripping hazard. | 9/15/2021 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door shall be self-closing and self-locking. | 9/15/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Provide a current tested fire extinguisher in the machine room. | 9/15/2021 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Provide code compliant ladder or steps to access elevated machine platform in machine room. | 9/15/2021 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current state operating certificate. | 9/15/2021 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Provide means to secure the emergency exit. | 9/15/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)4 | x | Counterweight buffers are rusted through and broken, will not support elevator. Red tagged, Re-inspection required | 1/16/2023 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit has at least 6" of water in it, needs to be kept clean & dry | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Governor rope is undersized, needs to be replaced. Re-inspection required | 1/16/2023 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Steps leading up to machine room need to be permanently installed with a handrail to prevent safety hazards | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Remove broken traveling cable in hoistway that's still attached to the bottom side of cab | |||
| MO Minimum : Elevators | (J) - Counterweights | (J)2 | Provide spin out cable through the rope shackles on the counterweights | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Repair or replace slide guide on left side of car. Guide is worn out and barely touches rail | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | Machine room shall be kept clean & free of debris and trash | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | x | Provide safe and convenient access to secondary level, proper steps w/handrail. SECOND NOTICE. | 9/5/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | x | Provide current tested (not new out of the box) fire extinguisher in the elevator machine room. | 9/5/2023 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | x | Existing hoist way doors require safety glass installed, provide proof that existing pane glass in hoist way door is CODE compliant. Numerous floors. | 9/5/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | x | Provide current year MCP. | 9/5/2023 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | x | Hoistway door sill catch on bottom floor needs to be secured to sill. | 9/5/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Several floors have the wired class panels, need to replace with solid glass, that is not etched or labeled. Provide proper labeling or replace if glass does not meet the ANSI requirements. | |||
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.12 | x | Need to replace defective governor, not operating properly | 3/19/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | 110.11a Need to secure 1st floor sill to floor | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door shall be self closing and self locking. | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | Machine room floor shall have open hole properly covered. | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Machine room shall be cleaned of trash and old broken elevator controller. | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Remove non elevator items from machine room. | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Remove broken light fixture from ceiling . | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher is expired. | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | Hoistway door glass shall be replaced with tempered glass. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Operating certificate shall be posted in machine room |