Inspection
Inspection Details
Equipment ID
24669
24669
Inspection Date
6/13/2025
6/13/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
545
545
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
18
18
External ID
7edba5a2-a224-4a04-9473-363e2259c907
7edba5a2-a224-4a04-9473-363e2259c907
Location
The Georgian
1418 Carroll St, St. Louis, MO
Phone: (314) 667-5913
1418 Carroll St, St. Louis, MO
Phone: (314) 667-5913
Owner
Attn: HG Pearl Georgian, LLC
HG Pearl Georgian, LLC
112 W Jefferson Blvd, Ste 200, South Bend, IN 46601
Phone: (314) 924-9502
HG Pearl Georgian, LLC
112 W Jefferson Blvd, Ste 200, South Bend, IN 46601
Phone: (314) 924-9502
Billing
Attn: Jessica Tarin- Property Manager
HG Pearl Georgian, LLC
1418 Carroll St, St. Louis, MO 63104
Phone: (314) 924-9502
Email: jessica@2bresidential.com
HG Pearl Georgian, LLC
1418 Carroll St, St. Louis, MO 63104
Phone: (314) 924-9502
Email: jessica@2bresidential.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 8/22/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be on display in the machine room | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work, appears not to have a live phone line. Re-inspection required | 5/9/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | 2-way communication device shall work with and without main power and give proper location. | 6/18/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 6/18/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | The machine room door shall be self-closing, self-locking, and operable from the interior space without the use of a key. | |||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency two way communication is inoperable. The phone shall be able to establish two communication. Repair or replace | 6/13/2025 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | x | Emergency battery lowering unit does not work. Repair or replace. REINSPECT IN 14 DAYS | 6/13/2025 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired, have serviced or replaced | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be on display in the machine room | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing, self-locking, and operable from the interior space without the use of a key. | |||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency two way communication is inoperable. The phone shall be able to establish two communication. Repair or replace | ||
A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | x | Emergency battery lowering unit does not work. Repair or replace. REINSPECT IN 14 DAYS |