Inspection
Inspection Details
Equipment ID
18417
18417
Inspection Date
6/17/2025
6/17/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Richard McCormack
Richard McCormack
Mechanic Name
Brian Smith
Brian Smith
Relief Valve Pressure
nana
nana
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
20
20
External ID
0db2c948-a01b-411e-a70a-855df88c5246
0db2c948-a01b-411e-a70a-855df88c5246
Location
Hawthorne Station
8700 HAWTHORNE RD, KANSAS CITY, MO
Phone: (816) 214-3409
8700 HAWTHORNE RD, KANSAS CITY, MO
Phone: (816) 214-3409
Owner
Attn: Renee Mosby
KC Power & Light
8700 Hawthorne Rd, Kansas City, MO 64120
Phone: (816) 242-3374
Alt Phone: (816) 242-3541
Email: Renee.Mosby@evergy.com
KC Power & Light
8700 Hawthorne Rd, Kansas City, MO 64120
Phone: (816) 242-3374
Alt Phone: (816) 242-3541
Email: Renee.Mosby@evergy.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean machine room. | 9/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | HVAC unit not working in machine room. | 9/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide up to date fire extinguisher in machine room. | 9/3/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in pit. | 9/3/2019 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Bottom final limit not working properly. It stops the elevator, but gets stuck in the open position. | 8/20/2019 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Bottom directional limit not working. | 8/20/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide an up to date fire extinguisher in machine room. No tag or date on the one provided. | 9/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | HVAC unit in machine room not cooling. | 9/6/2019 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 107.1b | Yes | No | runby less than 6 in | 7/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emg bell an lt not working | 7/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | need sump pump cover | 2/28/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working had no power | 7/7/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | current cirt not displayed | 2/28/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | mach. room lts not working no lt sw by entrance door | 2/28/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emg. phone not working | 8/23/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 8/28/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | door restrictor not working rear door | 8/16/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | no lt sw in machroom for lights to turn lts. on | 8/28/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | water on pit floor | 1/1/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach room door not self locking | 1/1/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 1/1/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | Water in pit. Repair sump pump | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | WATER FROM CONDENSATE LINE TO AC UNIT ON ELEVATOR FOOR | 8/20/2025 |