Inspection
Inspection Details
Equipment ID
16908
16908
Inspection Date
6/13/2025
6/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
Christopher McCarty
Christopher McCarty
Relief Valve Pressure
560
560
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
34c9edda-6820-4429-a03a-aa98403de619
34c9edda-6820-4429-a03a-aa98403de619
Location
Senior Livings & Gardens @ Renaissance
3217 Martin Luther King Dr, St. Louis, MO
Phone: (314) 652-8900
3217 Martin Luther King Dr, St. Louis, MO
Phone: (314) 652-8900
Owner
Attn: McCormack, Baron, Ragan
McCormack, Baron, Ragan
720 Olive St, St. Louis, MO 63101
Phone: (314) 652-8900
McCormack, Baron, Ragan
720 Olive St, St. Louis, MO 63101
Phone: (314) 652-8900
Billing
Attn: Blumeyer Elderly
Blumeyer Elderly
3217 Martin Luther King, St. Louis, MO 63106
Phone: (314) 652-8900
Email: renaissancesenior@mccormackbaron.com
Blumeyer Elderly
3217 Martin Luther King, St. Louis, MO 63106
Phone: (314) 652-8900
Email: renaissancesenior@mccormackbaron.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | In car emergency telephone shall work. | 5/21/2018 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept clean. | 3/1/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on this unit on or before the next annual inspection. | 3/24/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary battery lowering shall be operational. | 11/16/2022 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Where additional power sources is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. (Confirm operation and correct if needed). | 3/24/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 9/27/2023 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Yes | No | Where additional power source is connected to the load side of the disconnect, it shall have and auxiliary contact to prevent battery lowering from energizing when disconnect is opened. | 9/27/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State operating certificate in machine room. | 3/24/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Provide current tested fire extinguisher in machine room. | 3/24/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Machine room smoke detectors shall be operational. Smoke detector is currently covered and preventing it from being operational. | 9/27/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency light shall be operational. | 9/27/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up-to-date operating certificate required in machine room. | 3/24/2025 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Yes | No | Where additional power source is connected to the load side of the disconnect, it shall have and auxiliary contact to prevent battery lowering from energizing when disconnect is opened. | 6/12/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | The pit shall be kept clean. | 3/24/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/24/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary battery lowering shall be operational. |