Inspection
Inspection Details
Equipment ID
16891
16891
Inspection Date
6/16/2025
6/16/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
James Anderson
James Anderson
Mechanic Name
Nathaniel Smith
Nathaniel Smith
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
ebef2137-5bfa-4f7e-960f-db4bfddb58fd
ebef2137-5bfa-4f7e-960f-db4bfddb58fd
Location
St. Louis Busch Stadium
700 Clark Ave, St. Louis, MO
Phone: (314) 345-9404
Email: Hmaruyama@cardinals.com
700 Clark Ave, St. Louis, MO
Phone: (314) 345-9404
Email: Hmaruyama@cardinals.com
Owner
Attn: St. Louis Cardinals LLC
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
Billing
Attn: Hosei Maruyama
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hmaruyama@cardinals.com
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hmaruyama@cardinals.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair inoperative top demarcation light. | 1/7/2019 |
| conversion | conversion | n/a | No | No | Realign outter deck to close 1 inch gap in upper seam. | 1/7/2019 |
| conversion | conversion | n/a | No | No | comb impact guides are rusted and need to be tested to insure proper impact calibration. | 1/7/2019 |
| A17.1-1996 : Escalators | 7.9 - Steps and upthrust device | 802.5 | No | No | Replace broken step demarcation strip. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Repair left handrail that is cracked. | 3/29/2023 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Clean escalator truss space. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 1206.6 | No | No | Comb impact guides are rusted. Pressure test on tripping pressure needed. Reinspect within 30 days. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Replace left cracked handrail. | 7/2/2020 |
| A17.1-1996 : Escalators | 7.16 - Ceiling intersection guards | 802.3g | No | No | Replace wrong ceiling intersection guards with correct one. | 7/2/2020 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 802.6 | No | No | Replace broken step demarcations. | 7/2/2020 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 1206.6 | No | No | Step demarcation strip is broken on a couple steps | 6/28/2022 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 806 | No | No | Provide operating light at top end on unit. | 7/17/2025 |
| A17.1-1996 : Escalators | 8.13 - Handrail systems and safety devices | 802.4 | No | No | Replace main handrail drive chain | 7/17/2025 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Record maintenance, call backs, repairs, and testing in MCP and provide location of MCP on Escalator controller | 7/17/2025 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.4.1(d) | No | No | Record Step/Skirt Indexing Graph for 2025 in MCP. | 7/17/2025 |