Inspection
Inspection Details
Equipment ID
19491
19491
Inspection Date
12/18/2018
12/18/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
620
620
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
01084226-3893-4ad2-b820-9f296e20fe9e
01084226-3893-4ad2-b820-9f296e20fe9e
Location
Evans Commons
209 S. Kingshighway Street, St. Charles, MO
Phone: (000) 000-0000
209 S. Kingshighway Street, St. Charles, MO
Phone: (000) 000-0000
Owner
Lindenwood University
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301-1693
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301-1693
Billing
Attn: Lindenwood University
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301-1693
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301-1693
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | An MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 | 1/7/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 1/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 1/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation date of 2009, a category 5 test is due on the overspeed valve or before the next annual inspection. | 1/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | The auxiliary power lowering operation shall be functional. | 3/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 2.14.5 | Yes | No | The horizontal clearance shall not exceed .5" between the car side of the car door panel and the related car entrance jamb. Note: Both the right and left hand panels of this center opening car door fail to meet this requirement. The right hand car door, when in the normal open position, is open beyond the car entrance jamb, and because of this the clearance is several inches, and poses a potential pinch hazard. | 1/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room in a non-combustible frame with a clear protective vision plate over it. | 1/21/2026 |