Inspection
Inspection Details
Equipment ID
17547
17547
Inspection Date
6/3/2025
6/3/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
19f2d8d2-ec7d-4151-8fdd-355572b867a1
19f2d8d2-ec7d-4151-8fdd-355572b867a1
Location
Chase Park Plaza Hotel
212 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 633-1000
212 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 633-1000
Owner
Attn: Paul Smith
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1009
Alt Phone: (314) 363-4990
Email: psmith@sonesta.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1009
Alt Phone: (314) 363-4990
Email: psmith@sonesta.com
Billing
Attn: Accounts Payable
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: Psmith@Sonesta.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: Psmith@Sonesta.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the escalator at this time. The interior space shall be inspected before the inspection is completed. | 5/22/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(L) | No | No | A ceiling intersection guard is required on the left side of the escalator to prevent a pinch point for passengers | 3/31/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the escalator at this time. The interior space shall be inspected before the inspection is completed. | 6/3/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(L) | No | No | A ceiling intersection guard is required on the left side of the escalator to prevent a pinch point for passengers | 3/31/2026 |
| A17.1-2016 : Elevators | 8.5 - Speed governor | 8.6.8.15.5 | Yes | Yes | The speed governor cannot activate as designed and shall be repaired/replaced. Escalator is taken out of service with a red tag issued. | 6/3/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.4 Escalator Combplates | No | No | The bottom comb plate has a missing tooth and shall be replaced. | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(J) | No | No | A stop switch shall be provided in each machinery space where means of access to the space is provided. The switch when opened shall cause electric power to be removed from the escalator driving-machine motor and brake. The switch shall be of the manually opened and closed type and shall be marked “STOP.” | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | Step indexing is required to be performed. | 6/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the escalator, need to perform the following test to complete: The interior space shall be inspected. Re-inspection required | 6/25/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(L) | No | No | A ceiling intersection guard is required on the left side of the escalator to prevent a pinch point for passengers | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(J) | No | No | A stop switch shall be provided in each machinery space where means of access to the space is provided. The switch when opened shall cause electric power to be removed from the escalator driving-machine motor and brake. The switch shall be of the manually opened and closed type and shall be marked “STOP.” | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | Step indexing is required to be performed. | 6/25/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(L) | No | No | A ceiling intersection guard is required on the left side of the escalator to prevent a pinch point for passengers | 4/3/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(L) | No | No | A ceiling intersection guard shall be provided where the handrail meets the ceiling. Shall be 14" hotizontally from where the handrail meets the ceiling. |