Inspection
Inspection Details
Equipment ID
13389
13389
Inspection Date
12/21/2018
12/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Douglas Miller
Douglas Miller
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
14
14
External ID
f801e3ee-543a-4696-9bcc-80dafe7ef11b
f801e3ee-543a-4696-9bcc-80dafe7ef11b
Location
Welcome Center
209 S. Kingshighway Street, Saint Charles, MO
Phone: (000) 000-0000
209 S. Kingshighway Street, Saint Charles, MO
Phone: (000) 000-0000
Owner
Lindenwood University
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301-1693
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301-1693
Billing
Attn: Lindenwood University
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301-1693
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301-1693
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | An MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 | 1/7/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lights shall be operational. | 12/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The alarm bell shall operate on auxiliary power. | 12/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car top light shall be operational. | 1/7/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 1/31/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 1/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The car top light shall be operational. | 4/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The car-top lighting shall be operational. (2nd Notice) | 2/13/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The width of the working space of the main elevator disconnect shall in no case be less than the width of the disconnect. A surge suppressor has been mounted directly under the handle and immediately next to the disconnect. With the handle in the open position, it hits the suppressor. It shall be moved to meet the clearance requirements of NFPA 110.26. | 1/29/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The width of the working space of the main elevator disconnect shall in no case be less than the width of the disconnect. A surge suppressor has been mounted directly under the handle and immediately next to the disconnect. With the handle in the open position, it hits the suppressor. It shall be moved to meet the clearance requirements of NFPA 110.26. | 4/28/2025 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.11.3.1.3(b) | No | No | Car top light shall be operational. | 1/21/2026 |