Inspection
Inspection Details
Equipment ID
10874
10874
Inspection Date
12/20/2018
12/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
c4a35b53-c5bc-4971-b4c0-920216e72ac1
c4a35b53-c5bc-4971-b4c0-920216e72ac1
Location
Gallery 515
515 OLIVE ST, SAINT LOUIS, MO
515 OLIVE ST, SAINT LOUIS, MO
Owner
Brandonview LLC
515 OLIVE ST STE 106, SAINT LOUIS, MO 63101-1831
515 OLIVE ST STE 106, SAINT LOUIS, MO 63101-1831
Billing
Attn: Brandonview LLC
515 OLIVE ST STE 106, SAINT LOUIS, MO 63101-1831
515 OLIVE ST STE 106, SAINT LOUIS, MO 63101-1831
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.14 - Supply Piping | 8.11.3.1.5(i) | No | No | Supply piping in put has surface rust. Clean and examine to determine if replacement is needed. | 4/4/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 8.11.2.1.4(a) | No | No | Platform guard shall be replaced. (Currently incorrect size and partially detached from platform). | 4/4/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | North sidewalk door is missing safety chain. | 12/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | No | No | The penetrations in the hoistway wall near the bottom landing shall be sealed using approved material. | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. Where other existing machines and equipment essential to the operation and purpose of the building are located in the machine room or space, the elevator related equipment and machines shall be separated by a substantial grill constructed of noncombustible material not less than six feet (6') in height and the grill shall be of a design that will reject a ball two inches (2") in diameter. All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | The penetrations in the hoistway wall near the bottom landing shall be sealed with approved material. | 7/8/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. Where other existing machines and equipment essential to the operation and purpose of the building are located in the machine room or space, the elevator related equipment and machines shall be separated by a substantial grill constructed on non-combustible material not less than 6 feet high and the grill shall be of a design that will reject a ball 2 inches in diameter. All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | Yes | The hoistway walls shall be repaired or replaced to be structurally sound. Elevator Red Tagged. | 5/22/2026 |
| MO Minimum : Elevators | (P) - Existing Sidewalk Elevators | (P)4 | No | No | The broken chain on the trap door shall be repaired or replaced. | 7/8/2025 |