Inspection
Inspection Details
Equipment ID
11316
11316
Inspection Date
10/23/2018
10/23/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard Hawkins
Richard Hawkins
Relief Valve Pressure
Slide
7"
7"
Governor Rope Pull
60/800
60/800
Door Closing Force
25
25
External ID
25c57366-eb81-4fe7-bc25-fd84af9df0a3
25c57366-eb81-4fe7-bc25-fd84af9df0a3
Location
St. Louis Post Dispatch
900 N TUCKER BLVD, SAINT LOUIS, MO
900 N TUCKER BLVD, SAINT LOUIS, MO
Owner
St. Louis Post Dispatch
900 N TUCKER BLVD, SAINT LOUIS, MO 63101-1069
900 N TUCKER BLVD, SAINT LOUIS, MO 63101-1069
Billing
Attn: St. Louis Post Dispatch LLC
900 N TUCKER BLVD, SAINT LOUIS, MO 63101-1069
900 N TUCKER BLVD, SAINT LOUIS, MO 63101-1069
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Program emergency phone to ring to a 24 hr monitoring station. | 11/6/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Close holes at top of hoistway. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of construction. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | The signage for “In Case of Fire Use Stairs” is not located on all landings. Install signage that conforms to the building code this elevator was installed to meet. | 6/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 6/18/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 10/7/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. | 10/7/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/18/2025 |