Inspection
Inspection Details
Equipment ID
14908
14908
Inspection Date
12/18/2018
12/18/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Scott Tiemann
Scott Tiemann
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
7a27ee28-d8ce-4ff3-9215-15860475a6be
7a27ee28-d8ce-4ff3-9215-15860475a6be
Location
Courtyard by Marriott
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO
Owner
Courtyard by Marriott
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO 63146-3313
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO 63146-3313
Billing
Attn: Courtyard by Marriott
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO 63146-3313
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO 63146-3313
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Alarm bell shall work | 12/18/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light not working. | 8/12/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump from the pit and provide code compliant means of oil collection. | 9/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Provide emergency phones with correct car numbering. | 11/4/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Remove fluids from sump hole and determine if sump is working. | 9/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide written maintenance control program. | 9/6/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate. | 9/6/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Battery backup lowering unit not working correctly. | 11/2/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | Fire service operation shall work. Elevator Red Tagged. | 11/14/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in the machine room. | 11/14/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is due for Cat 5 test, last done in 2018 | 12/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm is not working, needs repaired. Re-inspection required | 9/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 12/9/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV in the pit is due for testing, provide. | 12/9/2025 |