Inspection
Inspection Details
Equipment ID
10239
10239
Inspection Date
12/17/2018
12/17/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
29
29
External ID
5607183d-ce6d-4fe8-91b6-de1f61928443
5607183d-ce6d-4fe8-91b6-de1f61928443
Location
Metropolitan Square
211 N BROADWAY, SAINT LOUIS, MO
211 N BROADWAY, SAINT LOUIS, MO
Owner
Metropolitan Square LLC
211 N BROADWAY, SAINT LOUIS, MO 63102-2721
211 N BROADWAY, SAINT LOUIS, MO 63102-2721
Billing
Attn: Jones Lang LaSalle
211 N BROADWAY STE 1290, SAINT LOUIS, MO 63102-2748
211 N BROADWAY STE 1290, SAINT LOUIS, MO 63102-2748
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work properly. | 7/21/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to test 125% brake test. Re-inspection required | 1/17/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to complete full load buffer test for car & counterweight. Re-inspection required | 1/17/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to test full load safety set. Re-inspection required | 1/17/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to test spin governor. Re-inspection required | 1/17/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The category 5 test was never completed and only a machine room inspection could be performed. The weight test shall be performed, safeties set, buffers compressed, door pressure, hoistway inspection, fireman’s emergency service, in car inspection, and emergency power operation tested before the inspection is completed. | 8/21/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Ph2 Call Cancel button shall be labeled, Ph2 Bezel shall be readable | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | Yes | Yes | Hoist ropes are undersized and have multiple broken strands across several ropes | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | Safety Rod Bushing shall be replaced (deteriorated) | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency Power needs to be tested | 9/22/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase 2 bezel shall be readable | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | Yes | No | Hoist ropes are undersized and have multiple broken strands across several ropes | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Safety Rod Bushings shall be replaced (deteriorated) |