Inspection
Inspection Details
Equipment ID
20214
20214
Inspection Date
6/16/2025
6/16/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
950
950
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
8ab2fd67-f7e5-42cc-9d1c-e9ce3bf95cec
8ab2fd67-f7e5-42cc-9d1c-e9ce3bf95cec
Location
Soho Towers
5438 Delmar Blvd, St. Louis, MO
Phone: (314) 367-7646
5438 Delmar Blvd, St. Louis, MO
Phone: (314) 367-7646
Owner
Attn: Multi-South Management Services
Soho Towers
5438 Delmar Blvd, St. Louis, MO 63112
Phone: (314) 637-7646
Soho Towers
5438 Delmar Blvd, St. Louis, MO 63112
Phone: (314) 637-7646
Billing
Attn: Michele McClanahan
Soho Towers
5340 Delmar Blvd, Apt 104, St. Louis, MO 63112
Phone: (314) 367-7646
Soho Towers
5340 Delmar Blvd, Apt 104, St. Louis, MO 63112
Phone: (314) 367-7646
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | In car phone does not work and shall be repaired and tested. | 12/4/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Provide documentation that unit does not have a single bottom cylinder. | 12/4/2018 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | No | No | 8.6.5.8 Determine if jack is single bottom type and provide documentation of findings on site. | 4/1/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 4/1/2021 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | No | No | Possible single bottom cylinder. If unit is double bottom type provide documentation that can be kept on site. If unit is single bottom, take corrective action. | 4/1/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | 4/1/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/16/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Keys were not available to test Fire Service. Keys shall be kept on site at all times. | 4/1/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Fire service shall be tested. | 2/16/2021 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | No | No | Possible single bottom cylinder. If unit is double bottom type provide documentation that can be kept on site. If unit is single bottom, take corrective action. | 4/1/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit needs to be cleaned. | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | The car top shall be cleaned. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Machine room shall be kept clean and free of debris. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Cab light disconnect switch in controller is broken. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light is not working. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |