Inspection
Inspection Details
Equipment ID
10245
10245
Inspection Date
12/19/2018
12/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
29
29
External ID
016c8798-ec0b-4380-a829-ab3185b47915
016c8798-ec0b-4380-a829-ab3185b47915
Location
Metropolitan Square
211 N BROADWAY, SAINT LOUIS, MO
211 N BROADWAY, SAINT LOUIS, MO
Owner
Metropolitan Square LLC
211 N BROADWAY, SAINT LOUIS, MO 63102-2721
211 N BROADWAY, SAINT LOUIS, MO 63102-2721
Billing
Attn: Jones Lang LaSalle
211 N BROADWAY STE 1290, SAINT LOUIS, MO 63102-2748
211 N BROADWAY STE 1290, SAINT LOUIS, MO 63102-2748
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are undersized. 60 day repair/reinspection required. | 7/21/2021 |
| MO Minimum : Elevators | (J) - Counterweights | (J)2 | No | No | Counterweight spin out cable is broken. Needs replacement within 30 days. Reinspection Required. | 8/19/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit door will not fully close. | 8/19/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit door does not fully close | 8/19/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test machine brake with 125% of rated load | 1/3/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car safety with rated load, rated speed | 1/3/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car buffer at rated speed, rated load | 1/3/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test counterweight buffer at rated speed | 1/3/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test phase 1 & 2 fire service | 1/3/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed. | 12/6/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 8/19/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Traction sheave liner is deteriorated and needs replacing | 8/19/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Down final limit switch roller is damaged and needs replacing | 8/19/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test elevator for operation on emergency power. Re-inspection required | 8/19/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Call cancel on Phase II fire service does not work, needs repaired. Re-inspection required | 8/19/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery backup, needs repaired. Re-inspection required | 8/19/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Traction sheave liner is deteriorated and needs replacing | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Emergency power was tested. Power did not transfer and selector did not operate and shall be repaired. |