Inspection
Inspection Details
Equipment ID
10247
10247
Inspection Date
12/19/2018
12/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
29
29
External ID
6a9f8ff2-faca-4ad1-8fe3-beb4afb92f24
6a9f8ff2-faca-4ad1-8fe3-beb4afb92f24
Location
Metropolitan Square
211 N BROADWAY, SAINT LOUIS, MO
211 N BROADWAY, SAINT LOUIS, MO
Owner
Metropolitan Square LLC
211 N BROADWAY, SAINT LOUIS, MO 63102-2721
211 N BROADWAY, SAINT LOUIS, MO 63102-2721
Billing
Attn: Jones Lang LaSalle
211 N BROADWAY STE 1290, SAINT LOUIS, MO 63102-2748
211 N BROADWAY STE 1290, SAINT LOUIS, MO 63102-2748
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Test car buffer at rated speed, rated load | 8/18/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Test counterweight buffer at rated speed | 8/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Test phase 1 & 2 fire service | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 12/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 12/6/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed. | 12/6/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 8/18/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery backup, needs repaired. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Traveling cable support (kellum) is broken at 22nd floor, needs to be replaced | 8/18/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test elevator for operation on emergency power. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Traveling cable is cracked and shall be replaced. Lack of spares is preventing car top inspection station from operating. Correct in conjunction with the T-cable | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Emergency power was tested. Power did not transfer and selector did not operate and shall be repaired. |