Inspection
Inspection Details
Equipment ID
10248
10248
Inspection Date
12/20/2018
12/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
28
28
External ID
c78d02d0-3f95-4e82-aab3-6b612f32f5a3
c78d02d0-3f95-4e82-aab3-6b612f32f5a3
Location
Metropolitan Square
211 N BROADWAY, SAINT LOUIS, MO
211 N BROADWAY, SAINT LOUIS, MO
Owner
Metropolitan Square LLC
211 N BROADWAY, SAINT LOUIS, MO 63102-2721
211 N BROADWAY, SAINT LOUIS, MO 63102-2721
Billing
Attn: Jones Lang LaSalle
211 N BROADWAY STE 1290, SAINT LOUIS, MO 63102-2748
211 N BROADWAY STE 1290, SAINT LOUIS, MO 63102-2748
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Test car buffer at rated speed, rated load | 8/18/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Test counterweight buffer at rated speed | 8/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Test phase 1 & 2 fire service | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 12/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 12/5/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. Emergency power operation shall be performed before the inspection is completed. | 12/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 8/18/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test elevator operation on emergency power. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work, needs repaired. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Down final limit switch roller is damaged and needs to be replaced | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Clean debris from compensation rope sheave groove in elevator pit | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Replace sheave liner on traction machine sheave due to wear. | 8/18/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery backup. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | 1 of the 2 door open buttons in the elevator cab does not work on Phase II fire service. Re-inspection required | 8/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Right COP door close button shall function during FEO Phase II. | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Governor rope shall be replaced due to kink and breaks. | |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Full Load safety slide did not meet the minimum slide distance. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Emergency power was tested. Power did not transfer and selector did not operate and shall be repaired. (60 days reinspect) |