Inspection
Inspection Details
Equipment ID
6181
6181
Inspection Date
6/18/2025
6/18/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
c0f75a56-5258-43a0-bc28-65d5341853c0
c0f75a56-5258-43a0-bc28-65d5341853c0
Location
Willert Home Products
4150 Park Ave, St. Louis, MO
Phone: (314) 772-2822
4150 Park Ave, St. Louis, MO
Phone: (314) 772-2822
Owner
Attn: Willert Home Products
Willert Home Products
4044 Park Ave, St. Louis, MO 63110
Phone: (000) 000-0000
Email: whptoolcrib@willert.com
Willert Home Products
4044 Park Ave, St. Louis, MO 63110
Phone: (000) 000-0000
Email: whptoolcrib@willert.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 6/22/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 9/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. This unit has no MCP in place. | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The fire extinguisher is expired. | 10/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in the machine room shall be not less than ten foot-candles at floor level. | 10/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. Where other existing machines and equipment essential to the operation and purpose of the building are located in the machine room or space, the elevator related equipment and machines shall be separated by a substantial grill constructed of noncombustible material not less than six feet (6') in height and the grill shall be of a design that will reject a ball two inches (2") in diameter. All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. Note: The machine and controller is in an open area above the hoistway without a door, access is unrestricted from the elevator lobby via a wooden ladder and does not meet these requirements. The door controls are also unrestricted, and located at the top floor and not in a separate room or space. | 10/15/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Remove the debris from pit. | 10/15/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | A permanent lighting fixture shall be provided in all pits to provide an illumination of net less than five foot-candles at the pit floor. The fixture switch shall be provided and accessible from the pit access door. | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 6/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting is not working. | 6/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | Yes | The in car emergency telephone shall be operational. Originally cited 5/30/24 and not compliant still. Elevator Red Tagged. | 10/15/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 10/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in the machine room shall be not less than 10 foot-candles at floor level. | 10/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. Where other existing machines and equipment essential to the operation and purpose of the building are located in the machine room or space, the elevator related equipment and machines shall be separated by a substantial grill constructed of noncombustible material not less than six feet (6') in height and the grill shall be of a design that will reject a ball two inches (2") in diameter. All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. Note: The machine and controller is in an open area above the hoistway without a door, access is unrestricted from the elevator lobby via a wooden ladder and does not meet these requirements. The door controls are also unrestricted, and located at the top floor and not in a separate room or space. | 10/14/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room access ladder - Top rung is loose and nails pulled out while climbing | 10/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Remove the debris from pit. | 10/14/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Cab lighting shall work. | 10/14/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)2 | No | No | Repair basement hoistway door. Upper door counterweight rope is broken. | 10/14/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (2nd Notice) | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. (2nd Notice) | 10/14/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in the machine room shall be not less than 10 foot-candles at floor level. (2nd Notice) | 10/14/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. Where other existing machines and equipment essential to the operation and purpose of the building are located in the machine room or space, the elevator related equipment and machines shall be separated by a substantial grill constructed of noncombustible material not less than six feet (6') in height and the grill shall be of a design that will reject a ball two inches (2") in diameter. All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. Note: The machine and controller is in an open area above the hoistway without a door, access is unrestricted from the elevator lobby via a wooden ladder and does not meet these requirements. The door controls are also unrestricted, and located at the top floor and not in a separate room or space. (2nd Notice) | 10/14/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room access ladder - Top rung is loose and nails pulled out while climbing. (2nd Notice) | 10/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Remove the debris from pit. (2nd Notice) | 10/14/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Cab lighting shall work. (2nd Notice) | 10/14/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)2 | No | No | Repair basement hoistway door. Upper door counterweight rope is broken. (2nd Notice) | 10/14/2025 |