Inspection
Inspection Details
Equipment ID
13130
13130
Inspection Date
6/27/2025
6/27/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Leland Jones
Leland Jones
Mechanic Name
Matthew Whaley
Matthew Whaley
Relief Valve Pressure
430
430
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
74acb8c1-b21b-4ffd-88fa-6f65f7d0ac94
74acb8c1-b21b-4ffd-88fa-6f65f7d0ac94
Location
Missouri Hospital Association
4712 Country Club Dr, Jefferson City, MO
Phone: (573) 893-3700
4712 Country Club Dr, Jefferson City, MO
Phone: (573) 893-3700
Owner
Attn: Missouri Hospital Association
Missouri Hospital Association
4712 Country Club Dr, Jefferson City, MO 65109
Phone: (000) 000-0000
Email: accountspayable@mhanet.com
Missouri Hospital Association
4712 Country Club Dr, Jefferson City, MO 65109
Phone: (000) 000-0000
Email: accountspayable@mhanet.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | No non-elevator related equipment can be stored in elevator equipment room | 11/11/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non elevator related items in machine room | 6/6/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. The car currently is not equipped with a telephone line, so the phone and the phone monitor could not be tested. | 5/22/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 5/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | The data on the door operator tag shall be filled out. | 5/22/2024 |
| A17.1-2016 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | Yes | No | The car-top emergency exit shall be secured to prevent it from falling down the hoistway. If a chain is used, it shall be not more than 12" in length and have a factor of safety of not less than 5. | 5/22/2024 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | 2.1.6.1 - The overhead fasteners protruding through the ceiling of the overhead shall be cut off flush to prevent a hazardous situation. | 5/22/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) | Yes | No | The in car keyed stop switch shall not be made ineffective on phase one fire service. | 5/22/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | ASME Interpretation - Record Number 10-1496. The sump pump controls shall not be located in the elevator machine room. Customer may apply for a variance. | 5/22/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. The machine room is currently a shared space for electrical switch gear and shelving. Customer may apply for a variance. | 5/22/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | ASME Interpretation - Record Number 10-1496. The sump pump controls shall not be located in the elevator machine room. Customer may apply for a variance. | 6/12/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. The machine room is currently a shared space for electrical switch gear and shelving. Customer may apply for a variance. | 6/12/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | MUST FILL ALL HOLES IN HOISTWAY |