Inspection
Inspection Details
Equipment ID
18762
18762
Inspection Date
6/26/2025
6/26/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Tommy Hogge
Tommy Hogge
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
e28ffa0e-b1b3-4f7b-affb-d9de4f257875
e28ffa0e-b1b3-4f7b-affb-d9de4f257875
Location
Horseshoe Casino
999 N 2nd St, St. Louis, MO
Phone: (314) 881-7782
999 N 2nd St, St. Louis, MO
Phone: (314) 881-7782
Owner
Attn: Andy Nowell
Horseshoe Casino
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-7782
Email: anowell@caesars.com
Horseshoe Casino
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-7782
Email: anowell@caesars.com
Billing
Attn: Andy Nowell
Horseshoe Casino
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-7782
Email: anowell@caesars.com
Horseshoe Casino
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-7782
Email: anowell@caesars.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Main COP alarm button not working. | 11/18/2019 |
| A17.1-2016 : Elevators | 1.3 - Operating control devices | 8.11.2.1.1(c) | No | No | Door close button not working | 12/8/2025 |
| A17.1-2016 : Elevators | 3.3 - Top-of-car operating device | 2.26.1.4 | No | No | Car top run station not functioning properly | 12/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working. Re-inspection required | 6/5/2025 |
| A17.1-2016 : Elevators | 11.14 - Terminal Stopping Devices | 2.25.2.2.1 | Yes | No | Down direction limit does not stop car before going onto final limit switch, repair needed. Re-inspection required | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | Emergency light & alarm are not working. Red-tagged, re-inspection required. | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Fire service Phase I operation instructions in main lobby are rubbed off, need to replace signage. | 12/8/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist belts are rouged. Acquire alteration permit and replace belts. Re-inspection required | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Door close button on main car operating panel still not working, needs to be replaced. | 12/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Elevator is overdue for Cat 5 testing. Need to perform the following tests to complete the inspection: Full load, full speed safeties, full load, full speed car buffer, full speed counterweight buffer, full load unintended movement, 125% brake lower and hold. Red-tagged until completed. Re-inspection required | 6/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | T Cable showing signs of wear. Repair or replace. | 12/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Fire service Phase I operation instructions in main lobby are rubbed off, need to replace signage. | 12/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Category 5 testing incomplete. Still needs full load, full speed safeties, 125% lower and hold, unintended motion, and car/counterweight buffers. | 6/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Phase I signage is worn off and needs replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | T Cable jacket is cracked and shall be repaired or replaced | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Phase I Fire Service light on hall keyswitch not working | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Machine room shall be cleaned. Remove old parts. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is out of date. |