Inspection
Inspection Details
Equipment ID
15135
15135
Inspection Date
7/1/2025
7/1/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Michael Scales
Michael Scales
Relief Valve Pressure
Na
Na
Slide
18”
18”
Governor Rope Pull
40/420
40/420
Door Closing Force
20
20
External ID
be9b14ca-cfce-447c-9323-6c86945440fa
be9b14ca-cfce-447c-9323-6c86945440fa
Location
Roosevelt Town Apts
711 N Euclid Ave, St. Louis, MO
Phone: (314) 361-7330
711 N Euclid Ave, St. Louis, MO
Phone: (314) 361-7330
Owner
Attn: Matt Kassel
LEDG Capital, LLC
10866 Wilshire Boulevard Suite 565, Los Angeles, CA 90024
Phone: (818) 632-0641
Email: msanders@winnco.com
LEDG Capital, LLC
10866 Wilshire Boulevard Suite 565, Los Angeles, CA 90024
Phone: (818) 632-0641
Email: msanders@winnco.com
Billing
Attn: Roosevelt Towne Apts
Roosevelt Towne Apts
711 N Euclid Ave, St. Louis, MO 63108
Phone: (228) 282-0308
Email: matt.kassel@ledgcapital.com
Roosevelt Towne Apts
711 N Euclid Ave, St. Louis, MO 63108
Phone: (228) 282-0308
Email: matt.kassel@ledgcapital.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Need Phase II fire service instructions in car | 5/29/2020 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Replace hoistway door rollers on floors 3,4 and 6. (Worn) | 5/29/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell and emergency light don't work in car. | 4/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Bulbs and tubes shall be guarded to prevent breakage | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide Phase II Fire Service Instructions on Car Operating Panel | 8/16/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Replace missing door closer spring on Second Landing hall door | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor is inoperable. When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening | 1/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 1/5/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 7/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, needs to be serviced or replaced. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean down the hoistway. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean the pit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Hoistway sill door closer, first floor, missing rod and spring. Repair or replace as needed. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Car emergency lights only one bulb working-2 required. |