Inspection
Inspection Details
Equipment ID
26504
26504
Inspection Date
7/7/2025
7/7/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
98f309a0-e6e5-42c6-ad20-e7009f4ef819
98f309a0-e6e5-42c6-ad20-e7009f4ef819
Location
8400 Delmar
8400 Delmar Blvd, University City, MO
Phone: (000) 000-0000
Email: leasing@mckenzie-lux.com
8400 Delmar Blvd, University City, MO
Phone: (000) 000-0000
Email: leasing@mckenzie-lux.com
Owner
Attn: McKenzie-Anna Purna One
McKenzie-Anna Purna One
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@luxliving.co
McKenzie-Anna Purna One
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@luxliving.co
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car. | 5/8/2024 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | Yes | No | 2.11.11.1(b) - Landing sills to be substantially flush with the floor surface of the elevator landings. | 5/8/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Top of hoistway:(2) 4 x 4 boxes are missing KO plugs. | 5/8/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Pit: (1) 4 x 4 box is missing KO plugs. | 5/8/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Pit: Lighting conduit needs to be secured. | 5/8/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | Yes | No | Pit sump pump cover is required. | 5/8/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | Yes | No | 2.2.4.2.4 - A clear distance of not less than 115 mm from the centerline of the rungs, cleats, or steps to the nearest permanent object in back of the ladder shall be provided. | 5/8/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating Certificate shall be posted in machine room. | 4/16/2025 |
| A17.1-2016 : Elevators | 3.14 - Hoistway clearances | 2.5 | No | No | Front door clutch shall have proper clearance to hoistway sill. Clutch is striking the hoistway sill on multiple floors. | 4/16/2025 |
| A17.1-2016 : Elevators | 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators | 2.27.1 | Yes | No | Phase 1 operating instruction shall be posted in hall. | 7/7/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Emergency Light shall be operation and lens replaced (led board is bad) | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel | Yes | No | Phase II, Rear door open and door close shall operate only with continuous pressure. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Machine roomless battery rescue operation (Schindler PEBO) shall be made operational. |