Inspection
Inspection Details
Equipment ID
8772
8772
Inspection Date
7/1/2025
7/1/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Andrew Schmitz
Andrew Schmitz
Relief Valve Pressure
455
455
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
10
10
External ID
ad394bc4-dc41-4ae2-8cb0-0088d52eaf3b
ad394bc4-dc41-4ae2-8cb0-0088d52eaf3b
Location
NPIF2 13600 Shoreline Dr LLC
13600 Shoreline Dr, Earth City, MO
Phone: (816) 888-7873
13600 Shoreline Dr, Earth City, MO
Phone: (816) 888-7873
Owner
Attn: Liz Brown
NPIF2 13600 Shoreline Dr LLC
4825 NW 41st St, Ste 500, Riverside, MO 64150
Phone: (636) 346-9800
Email: ebrown@northpointkc.com
NPIF2 13600 Shoreline Dr LLC
4825 NW 41st St, Ste 500, Riverside, MO 64150
Phone: (636) 346-9800
Email: ebrown@northpointkc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. 1.6 | 7/13/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is not sealed and needs full load test and tripping speed checked. Re-inspection required | 9/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 1/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator. | 1/30/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired. Replace or have serviced | 1/30/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Battery lowering device is not working. Re-inspection is required | 1/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit | 1/30/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/30/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work | 12/11/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Current Fire Extinguisher is expired and shall be replaced with a valid fire extinguisher. | 7/30/2026 |