Inspection
Inspection Details
Equipment ID
14314
14314
Inspection Date
7/10/2025
7/10/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Relief Valve Pressure
00
00
Slide
Governor Rope Pull
Door Closing Force
00
00
External ID
9fcc9642-79f4-4798-9743-d6b3dab8c3dd
9fcc9642-79f4-4798-9743-d6b3dab8c3dd
Location
City View Lofts LLC
201 S 10th St, St. Joseph, MO
Phone: (816) 368-2013
201 S 10th St, St. Joseph, MO
Phone: (816) 368-2013
Owner
Attn: Shannon Marsh
Paxe St Joseph Apartments LLC
201 S 10th St, St. Joseph, MO 64501
Phone: (816) 368-2013
Email: manager@saintjosephapts.com
Paxe St Joseph Apartments LLC
201 S 10th St, St. Joseph, MO 64501
Phone: (816) 368-2013
Email: manager@saintjosephapts.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | Phone inside elevator does not operate. | 6/25/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | 5/3/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | Photocell door reopening device does not function | 5/3/2022 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | x | No visual signal (fore hat) during phase 1 recall | 5/3/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Test and log firefighter operation monthly | 2/15/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Remove debris on car top. | 2/15/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | Remove debris from pit | 2/15/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | Remove debris from machine room floor | 2/15/2022 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Reattach pit light fixture to mounting box. | 2/15/2022 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No state operating certificate on site. Post current state operating certificate inside the machine room | 2/15/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Maintenance record log not up to date | 7/1/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | EMERGENCY LIGHTS DOES NOT WORK | 7/1/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | ENTIRE JOB NEED CLEANED | 7/1/2025 |