Inspection
Inspection Details
Equipment ID
13534
13534
Inspection Date
6/1/2017
6/1/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
29
29
External ID
13534
13534
Location
Mallincrodt Bldg
3600 North 2nd St, St. Louis, MO
Phone: (314) 654-1768
3600 North 2nd St, St. Louis, MO
Phone: (314) 654-1768
Owner
Covidien
3600 North 2nd St, St Louis, MO 63147
3600 North 2nd St, St Louis, MO 63147
Billing
Attn: Covidien
3600 North 2nd St, , MO 63147
3600 North 2nd St, , MO 63147
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current MO State certificate in machine room | 2/26/2021 |
| conversion | conversion | n/a | No | No | Machine room must be kept clean of materials not involved with the elevator operation | 2/26/2021 |
| conversion | conversion | n/a | No | No | Car door skins need repaired | 2/26/2021 |
| conversion | conversion | n/a | No | No | Pit must be kept clean and free of oil | 2/26/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Post current Mo state certificate in machine room | 2/26/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Car door skins need repair | 2/26/2021 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)1 | No | No | Repair/replace south fast car door | 2/26/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machin room | 2/26/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 2/26/2021 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | repair phone in car | 5/4/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room, | 2/26/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 8/9/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform month fire service testing & document on log in machine room | 2/26/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Need Mcp on site indicating testing procedures located in machine room | 11/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Need to remove oil transfer pump in pit | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Need prints for this unit in machine room | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 12/15/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove all non-elevator related materials from the machine room. | 12/15/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Jack head drain tube shall be routed to a measurable container in pit. Pit scavenger pump will be removed. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | Yes | No | Need wiring diagrams for this unit in the machine room. REINSPECTION TO ENFORCE. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Car door to door gaps are excessive | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Car door to return jamb gaps are excessive | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Hallway door guides shall engage sill by not less than 1/4" (floor 5). Also verify door to sill is less than 1/2" | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept dry. Remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak. |