Inspection
Inspection Details
Equipment ID
26921
26921
Inspection Date
6/18/2025
6/18/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Tim Switzer
Tim Switzer
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
aee9a707-0726-4cee-8011-0f15cd864445
aee9a707-0726-4cee-8011-0f15cd864445
Location
DEVON STORAGE ST LOUIS
4222 UNION BLVD, St. Louis, MO
Phone: (888) 553-3866
Email: terry@ramgcd.com
4222 UNION BLVD, St. Louis, MO
Phone: (888) 553-3866
Email: terry@ramgcd.com
Owner
Attn: DEVON SELF STORAGE
DEVON SELF STORAGE
2000 POWELL ST STE 1240, EMERYVILLE, CA 94608
Phone: (888) 553-3866
Email: terry@ramgcd.com
DEVON SELF STORAGE
2000 POWELL ST STE 1240, EMERYVILLE, CA 94608
Phone: (888) 553-3866
Email: terry@ramgcd.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Install emergency two-way communications device in car. | 6/18/2025 |
| A17.1-2016 : Elevators | 3.3 - Top-of-car operating device | 2.14.1.7 | Yes | No | Install railing on cartop. | 6/18/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | Yes | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 6/18/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/18/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Replace flexible metal conduit with EMT from fire alarm system relays to elevator controllers in machine room. Cannot be longer than 6" in length. | 6/18/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Replace flexible metal conduit with EMT from disconnect to climate control unit in machine room. Cannot be longer than 6" in length. | 6/18/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | Yes | No | Patch holes and voids in machine room especially at top of walls and where piping passes through to hoistway. | 6/18/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | Yes | No | Fire caulk and fill voids around hoistway side of entrance frames. | 6/18/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | Yes | No | Fire caulk and seal around room side of hoistway entrance frames. | 6/18/2025 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | Remove old unused sprinkler piping from top of hoistway. | 6/18/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | Yes | No | Cover hole where hydraulic supply line and sump pump discharge line pass through hoistway wall between pits at pit floor level. | 6/18/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 3.1 | Yes | No | Patch holes on hoistway side of wall where hydraulic supply line passes into machine room. | 6/18/2025 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | Top of common wall between hoistways shall be beveled no less than 75 degrees. | 6/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Box on 1st floor that hall station is mounted to needs to be replaced with a deeper box so hall station plate will fit flush with no gap. | 6/18/2025 |