Inspection
Inspection Details
Equipment ID
20287
20287
Inspection Date
7/15/2025
7/15/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Michael Collumbien
Michael Collumbien
Relief Valve Pressure
510
510
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
15
15
External ID
c5d28a96-6a28-41e9-ac69-abf296cd0893
c5d28a96-6a28-41e9-ac69-abf296cd0893
Location
Joint Armed Forces
24 Davis St, St. Louis, MO
Phone: (314) 416-6600
24 Davis St, St. Louis, MO
Phone: (314) 416-6600
Owner
Attn: Joint Armed Forces
Joint Armed Forces
24 Davis St, St. Louis, MO 63125
Phone: (000) 000-0000
Joint Armed Forces
24 Davis St, St. Louis, MO 63125
Phone: (000) 000-0000
Billing
Attn: Missouri Army National Guard-INTERAGENCY
Missouri Army National Guard-INTERAGENCY
8619 N Boundary Rd, Jefferson City, MO 65101
Phone: (000) 000-0000
Missouri Army National Guard-INTERAGENCY
8619 N Boundary Rd, Jefferson City, MO 65101
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test document on log in machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide maintenance control program | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency light | 12/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone in car | 12/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Make repairs for level stopping of the car | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repalce broken floor tile at 1st floor car entrance/ tripping hazard | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.7 - Car leveling and anticreep devices | 2.26.1.6 | No | No | adjust elevator for level stopping | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 8/29/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone works, provide connection to current contractor. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide updated MCP. |