Inspection
Inspection Details
Equipment ID
7176
7176
Inspection Date
12/28/2018
12/28/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Timothy Roberts
Timothy Roberts
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
17
17
External ID
07fae479-315a-4b4d-bd75-05578486138a
07fae479-315a-4b4d-bd75-05578486138a
Location
Ford Bldg
1405 PINE ST, SAINT LOUIS, MO
1405 PINE ST, SAINT LOUIS, MO
Owner
Ford Building
1405 PINE ST, SAINT LOUIS, MO 63103-2328
1405 PINE ST, SAINT LOUIS, MO 63103-2328
Billing
Attn: Ford Building Land Lord LLC
393 N EUCLID AVE STE 300, SAINT LOUIS, MO 63108-1239
393 N EUCLID AVE STE 300, SAINT LOUIS, MO 63108-1239
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | Suspension ropes are below minimum diameter. Replace and reinspect within 30 days. | 1/27/2020 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | ||
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | The fire tabs (Hoistway Door Safety Retainers) is not installed on the top hoistway door. The fire tab shall be installed to retain the hoistway doors in the closed position if the primary means fails. | |||
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | |||
MO Minimum : Elevators | (I) - Pits | (I)7 | The enclosed stop switch in the pit shall meet A17.1 1995 which requires the switch to be marked red. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The signage for “In Case of Fire Use Stairs” is not located on the bottom landing. Install signage that conforms to the building code this elevator was installed to meet. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2023 | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | The elevator car top shall be cleaned of spare parts. | |||
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The counterweight guides shall be adjusted to provide adequate clearance when the counterweight travels to the top of the hoistway. Currently the guides are rubbing excessively on the guide rail. | |||
A17.1-1996 : Elevators | 3.5 - Normal terminal stopping device | 209.2 | x | The normal terminal stopping device when activated initially stops the car as required. However, after a slight pause, the elevator continues up onto the final limit. Repair and reinspection required in 30 days. |