Inspection
Inspection Details
Equipment ID
26826
26826
Inspection Date
6/30/2025
6/30/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Shane Warth
Shane Warth
Relief Valve Pressure
NA
NA
Slide
6"
6"
Governor Rope Pull
20/210
20/210
Door Closing Force
18
18
External ID
1ce921e2-2b4b-4dfe-b943-6f50b47c0091
1ce921e2-2b4b-4dfe-b943-6f50b47c0091
Location
St. Charles Community College RWIC
2400 Interstate Dr, Wentzville, MO
Phone: (000) 000-0000
Email: ntrentman@rccllc.com
2400 Interstate Dr, Wentzville, MO
Phone: (000) 000-0000
Email: ntrentman@rccllc.com
Owner
Attn: St. Charles Community College
St. Charles Community College
4601 Mid Rivers Mall Dr, Cottleville, MO 63376
Phone: (000) 000-0000
Email: ntrentman@rccllc.com
St. Charles Community College
4601 Mid Rivers Mall Dr, Cottleville, MO 63376
Phone: (000) 000-0000
Email: ntrentman@rccllc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Machine room door shall be self-closing and self-locking. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Machine room door shall have smoke seal around the door. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.1.3 | Yes | No | Relocate duct smoke detector reset switch to outside machine room. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | Yes | No | Fill smoke/fire penetrations with approved fire caulk. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Mainline and lighting disconnects need labeling for purpose of each. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | n/a | Yes | No | NEC 110.26 - Machine room lighting disconnect does not meet 30" rule/not co-planer. | 6/30/2025 |
| A17.1-2016 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 2.26 | Yes | No | Machine room lighting disconnect has a fused neutral. | 6/30/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Fire caulk/fill holes and voids in hoistway walls. | 6/30/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Hoistway sills shall be flush with flooring, currently > 1" gap b/w sill and flooring. | 6/30/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.4 | Yes | No | Pit sump pump controller shall be relocated to outside the pit. | 6/30/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | Yes | No | Phase 1 fire hat does not work. | 6/30/2025 |