Inspection
Inspection Details
Equipment ID
15707
15707
Inspection Date
7/18/2025
7/18/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Christopher Davis
Christopher Davis
Relief Valve Pressure
400
400
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
11ebd032-0778-4bf5-a3b3-60038e78f3cc
11ebd032-0778-4bf5-a3b3-60038e78f3cc
Location
8th & Pine West
323 S 8th St, St. Louis, MO
Phone: (314) 982-1400
323 S 8th St, St. Louis, MO
Phone: (314) 982-1400
Owner
Attn: Metro Accounts Payable
Metro Accounts Payable
707 N 1st St, St. Louis, MO 63102
Phone: (314) 982-1400
Email: eastefano@MetroStLouis.org
Metro Accounts Payable
707 N 1st St, St. Louis, MO 63102
Phone: (314) 982-1400
Email: eastefano@MetroStLouis.org
Billing
Attn: Metro Accounts Payable
Metro Accounts Payable
PO Box 1349, St. Louis, MO 63188
Phone: (314) 982-1400
Email: dxstill@MetroStLouis.org
Metro Accounts Payable
PO Box 1349, St. Louis, MO 63188
Phone: (314) 982-1400
Email: dxstill@MetroStLouis.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need "Low Overhead" clearly posted in hoistway | 12/14/2018 |
| conversion | conversion | n/a | No | No | Post MO State operating permit in machine room | 12/14/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Cab ventilation not working. | 9/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light not working. | 6/15/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room shall not be used for storage of non-elevator equipment. | 9/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | AC unit cannot be located directly over the pump unit in the elevator machine room. Move AC unit | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Condensation line cannot be mounted over the pump unit in the elevator machine room. Move line | 11/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.19 - Guide rails fastening and equipment | 8.11.2.1.3(y) | No | No | Slide guides on the car top have excessive play and lateral movement. Adjust, replace, or repair slide guides | 11/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | No | No | Repair leaking victaulic pipe fitting inside the pump unit in the maching room. | 11/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 8.11.2.1.5(f) | No | No | Both traveling cables are rubbing conduit in the hoistway. Move cables to prevent damage | 10/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Car light disconnect is located 9 feet up. Lower disconnect to where it is accessible | 11/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 2.8.1 | No | No | Both traveling cables are rubbing conduit in elevator hoistway. Move cables to prevent further damage | 10/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Air conditioning systems shall not be located directly over elevator equipment. | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Safety retainers are missing on top and bottom hoistway doors, need to install safety retainers. Re-inspection required | 10/4/2024 |