Inspection
Inspection Details
Equipment ID
5721
5721
Inspection Date
7/18/2025
7/18/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Steven Crim
Steven Crim
Relief Valve Pressure
450
450
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
3ef783e0-071d-47e9-9c7e-1f2851bc7935
3ef783e0-071d-47e9-9c7e-1f2851bc7935
Location
Monroe City Middle School
430 N WASHINGTON ST, MONROE CITY, MO
Phone: (573) 735-4631
430 N WASHINGTON ST, MONROE CITY, MO
Phone: (573) 735-4631
Owner
Attn: Monroe City R-1 School District
Monroe City R-1 School District
401 Hwy 24 & 36 E, Monroe City, MO 63456
Phone: (000) 000-0000
Email: erodgers@monroe.k12.mo.us
Monroe City R-1 School District
401 Hwy 24 & 36 E, Monroe City, MO 63456
Phone: (000) 000-0000
Email: erodgers@monroe.k12.mo.us
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non-elevator related items out of machine room. | 8/17/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean machine room floor. Excessive dirt and debris present at time of inspection. | 8/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide MCP in machine room. Maintenance Control Program to log maintenance, repairs, and inspections. | 8/17/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related items from machine room. Brooms, etc. | 8/17/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/17/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide self locking mechanism for machine room door. Lock cylinder has been removed. | 8/17/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 8/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP needed | 8/17/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room | 8/17/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 8/17/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current operating certificate needed | 8/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Bldg line | 8/17/2026 |