Inspection
Inspection Details
Equipment ID
8229
8229
Inspection Date
12/12/2017
12/12/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Relief Valve Pressure
530
530
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
Location
The Crossings Church
115 May Rd, Wentzville, MO
Phone: (636) 497-6909
115 May Rd, Wentzville, MO
Phone: (636) 497-6909
Owner
The Crossings Church
115 May Rd, Wentzville, MO 63385
115 May Rd, Wentzville, MO 63385
Billing
Attn: The Crossings Church
115 May Rd, , MO 63385
115 May Rd, , MO 63385
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | In car emergency telephone shall work. | 10/30/2018 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 10/24/2019 | |
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/3/2023 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 8/11/2023 | |
A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | Machine room is only for elevator materials. Remove all non-elevator related materials. | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |||
A17.1-1996 : Elevators | 1.3 - Operating control devices | 210.1a | The hall call buttons shall be accessible. Note: Buttons are currently taped over. | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | x | 2-way communication device shall work (with and without main power) and give proper location. Violation cited originally on 12/19/22 and still not operational. Elevator is Red Tagged. | 8/29/2023 |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 210.1a | The hall call buttons shall be accessible. Note: Buttons are currently taped over as a "child-proof" measure. Hall calls shall be of proper design and construction. This is a multi-year self certify violation. If not complied with prior to the next annual inspection, the violation will require a re-inspection. | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. Not present in the machine room at this time. | |||
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Machine room cab light disconnect shall work properly and be of a lockable style. Currently unable to turn off cab lights due to damaged switch. | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Machine room shall have proper fire extinguisher and shall have a current test tag. Note: Extinguisher is expired. |