Inspection
Inspection Details
Equipment ID
170
170
Inspection Date
7/23/2025
7/23/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Andrew Schmitz
Andrew Schmitz
Relief Valve Pressure
390
390
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
19eca7ac-fdb4-4be2-a980-5459d22a9c15
19eca7ac-fdb4-4be2-a980-5459d22a9c15
Location
Emerson Corporate Office
8000 W Florissant Ave, St. Louis, MO
Phone: (314) 553-2229
Email: Jeff.chapin@emerson.com
8000 W Florissant Ave, St. Louis, MO
Phone: (314) 553-2229
Email: Jeff.chapin@emerson.com
Owner
Attn: Jeff Chapin
Emerson Corporate Office
8000 W Florissant, St. Louis, MO 63136
Phone: (314) 623-6003
Alt Phone: (314) 568-4569
Email: Jeff.chapin@emerson.com
Emerson Corporate Office
8000 W Florissant, St. Louis, MO 63136
Phone: (314) 623-6003
Alt Phone: (314) 568-4569
Email: Jeff.chapin@emerson.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | Replace missing chains on freight door access on 2nd & 3rd floors to access top of elevator. | 9/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | Replace missing pull chains on freight door access on 2nd & 3rd floors to access top of elevator | 2/23/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current copy of the state operating certificate shall be displayed in machine room | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher in machine room is expired. Replace or have serviced. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 2.12.6 | No | No | Replace missing pull chains on freight door access on 3rd floor to access top of elevator | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | No | No | The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | No | No | The car top escape hatch shall be secured closed and shall be openable without the use of special tools. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | One light fixture failed to operate on the day of testing, repair light fixture. | 2/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Hoistway access pull chain on the top landing shall be repaired or replaced. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | Auxiliary lighting inoperable and shall be repaired or replaced. | 3/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | Can lighting only has one operating bulb. Repair or replace to ensure all can lighting is operable. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Hoistway access pull chain on the top landing shall be repaired or replaced. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | Phase 2 operation failed, reinspection required. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | Auxiliary lighting inoperable, repair or replace as needed. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell inoperable during auxiliary power,and shall be repaired or replaced. | 2/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light is inoperable. Re-inspection required | 9/16/2026 |